Formula (uP): Upper target position = Start position (A1.STPOS) ± Start tolerance
(A2.STTOL) + Stroke height (A3.STRKH)
do: Actuator only moves downward
The actuator moves from its start position to the lower target
position.
After reaching the lower target position, the actuator moves
back to the start position.
Formula (do): Low target position = Start position (A1.STPOS) ± Start tolerance
(A2.STTOL) - Stroke height (A3.STRKH)
uP do: Actuator moves up and down
The actuator first moves from its start position to the upper target
position.
It then moves from the upper target position to the lower target
position.
After reaching the lower target position, the actuator moves
back to the start position.
Formula (uP do) Target position = Start position (A1.STPOS) ± Start tolerance
(A2.STTOL) ± Stroke height (A3.STRKH)
Factory setting: do
A5.RPMD - Ramp mode
Setting options: OFF
On
Purpose: Enable or disable ramp mode.
OFF: The partial stroke test is executed in an uncontrolled
manner.
On: The partial stroke test is executed in a controlled manner.
Control is at the ramp rate set in the "A6.RPRT" parameter.
Use ramp mode to shorten or extend the time of the partial stroke
test. Extend the partial stroke test to give the higher-level control
loop a chance to react to the partial stroke test.
Factory setting: OFF
A6.RPRT - Ramp rate
Adjustment range: 0.1 ... 100.0
Purpose: Change the ramp rate to shorten or extend the duration of the partial
stroke test. The ramp rate refers to the total stroke of the control valve
and is set in % stroke per second (%/s). Smaller values extend the
duration, larger values shorten the duration of the partial stroke test.
Example: Setting "10.0" means that the partial stroke test is run with
10% stroke per second.
Factory setting: 1.0
Parameter assignment
8.3 Description of parameters
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC 165

Table of Contents

Other manuals for Siemens SIPART PS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 and is the answer not in the manual?

Siemens SIPART PS2 Specifications

General IconGeneral
Supply Pressure1.4 to 7 bar (20 to 100 psi)
Enclosure RatingIP66/NEMA 4X
Communication ProtocolsHART, PROFIBUS PA, FOUNDATION Fieldbus
Output Pressure0 to 100% of supply pressure
Hazardous Area CertificationATEX, IECEx, FM, CSA
TypeElectropneumatic
Input Signal4-20 mA
Rotation Angle30° to 90°
Operating Temperature-40°C to +80°C
MountingLinear and rotary actuators
Air ConsumptionTypically less than 0.1 kg/h