EasyManuals Logo

Siemens SIPART PS2 User Manual

Siemens SIPART PS2
372 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #187 background imageLoading...
Page #187 background image
P4.LEVL2 - threshold 2
Possible settings: 0.1 ... 100.0
Purpose: Use this sub-parameter to set threshold 2 for the maximum devia‐
tion of the current average value of position from the average value
of reference. The value is given in percent. Set the threshold in a
range from '0.1' to '100.0'.
The positioner triggers the threshold 2 message if the difference
between the average value of position and the average value of
reference exceeds threshold 2. This message is only output if
threshold 3 is not exceeded at the same time. The process to acti‐
vate and display this message is described in the 'XDIAG' param‐
eter.
Factory setting: 5.0
P5.LEVL3 - threshold 3
Possible settings: 0.1 ... 100.0
Purpose: Use this sub-parameter to set threshold 3 for the maximum devia‐
tion of the current average value of position from the average value
of reference. The value is given in percent. Set the threshold in a
range from '0.1' to '100.0'.
The positioner triggers the threshold 3 message if the difference
between the average value of position and the average value of
reference exceeds threshold 3. The process to activate and display
this message is described in the 'XDIAG' parameter.
Factory setting: 10.0
Parameter assignment
8.3 Description of parameters
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC 187

Table of Contents

Other manuals for Siemens SIPART PS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 and is the answer not in the manual?

Siemens SIPART PS2 Specifications

General IconGeneral
Supply Pressure1.4 to 7 bar (20 to 100 psi)
Enclosure RatingIP66/NEMA 4X
Communication ProtocolsHART, PROFIBUS PA, FOUNDATION Fieldbus
Output Pressure0 to 100% of supply pressure
Hazardous Area CertificationATEX, IECEx, FM, CSA
TypeElectropneumatic
Input Signal4-20 mA
Rotation Angle30° to 90°
Operating Temperature-40°C to +80°C
MountingLinear and rotary actuators
Air ConsumptionTypically less than 0.1 kg/h