Different status and diagnostics messages can be allocated to individual diagnostics events as
per the following tables. The frame in which an allocation is possible is defined by the group in
the selection column. The following principle is used: in case of three-stage diagnostics events
of the MAINTENANCE group, the effect of the higher lever events can be downgraded, but that
of the lower level events cannot be upgraded.
DIAGNOSTICS_EXTENSION physical block parameter
Byt
e
Bit No. Diagnostics events Effect of the event
1)
Group
Quality status code DIAGNOSTICS bit
0 0 1 Run time error of the ac‐
tuator
Good, Ok DIA_MAINTENANCE_ALARM M
1 2 The device is not in the
"Automatic mode"
Good, check function /
manual mode
DIA_FUNCTION_CHECK F
2 3 Binary 1 is active (only
message)
Good, Ok DIA_MAINTENANCE_DEMAN‐
DED
M, F, P
3 4 Action triggered by bina‐
ry input 1
Good, Ok DIA_FUNCTION_CHECK M, F, P
4 5 Binary 2 is active (only
message)
Good, Ok DIA_MAINTENANCE_DEMAN‐
DED
M, F, P
5 6 Action triggered by bina‐
ry input 2
Good, Ok DIA_FUNCTION_CHECK M, F, P
7 ... 21 Reserved - - -
2 5 22 Limit for alarm A1 ex‐
ceeded
Good, maintenance re‐
quirement
DIA_MAINTENANCE None, hard-co‐
ded
6 23 Limit for alarm A2 ex‐
ceeded
Good, maintenance re‐
quirement
DIA_MAINTENANCE None, hard-co‐
ded
7 24 Error in the device elec‐
tronic unit
Bad, maintenance re‐
quirement
DIA_MAINTENANCE_ALARM None, hard-co‐
ded
Functions/operations using PROFIBUS PA
9.3 Cyclic data transfer
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC 231