Byt
e
Bit No. Diagnostics events Effect of the event
1)
Quality status code DIAGNOSTICS bit Group
4 0 81 Permissible device tem‐
perature exceeded (lim‐
it 1)
Uncertain, process
fault, no maintenance
required
DIA_INV_PRO_COND M1, P
1 82 Permissible device tem‐
perature exceeded (lim‐
it 2)
Uncertain, process
fault, no maintenance
required
DIA_INV_PRO_COND M12, P
2 83 Permissible device tem‐
perature exceeded (lim‐
it 3)
Uncertain, process
fault, no maintenance
required
DIA_INV_PRO_COND M, P
3 84 Permissible device tem‐
perature undershot (lim‐
it 1)
Uncertain, process
fault, no maintenance
required
DIA_INV_PRO_COND M1, P
4 85 Permissible device tem‐
perature undershot (lim‐
it 2)
Uncertain, process
fault, no maintenance
required
DIA_INV_PRO_COND M12, P
5 86 Permissible device tem‐
perature undershot (lim‐
it 3)
Uncertain, process
fault, no maintenance
required
DIA_INV_PRO_COND M, P
6 87 Limit for dead zone mon‐
itoring exceeded
Uncertain, maintenance
demand
DIA_MAINTENANCE_ALARM M
88 ...
96
Reserved - - -
1)
Effects of the event can be set using the DIAG_EVENT_SWITCH or DIAG_EVENT_SWITCH_2 parameters (default
settings in this case)
Functions/operations using PROFIBUS PA
9.3 Cyclic data transfer
SIPART PS2 with PROFIBUS PA
234 Operating Instructions, 05/2019, A5E00127926-AC