Addr. Parameter Setting Options Default Setting Comments
8507 MEAS. VALUE 4< Disabled
Ua
Ub
Uc
Ud
Ue
Uf
Disabled Measured Value for Threshold
MV4<
8508 THRESHOLD MV4< 2 .. 200 % 100 % Pickup Value of Measured Value
MV4<
8509 MEAS. VALUE 5> Disabled
Ua
Ub
Uc
Ud
Ue
Uf
Disabled Measured Value for Threshold
MV5>
8510 THRESHOLD MV5> 2 .. 200 % 100 % Pickup Value of Measured Value
MV5>
8511 MEAS. VALUE 6< Disabled
Ua
Ub
Uc
Ud
Ue
Uf
Disabled Measured Value for Threshold
MV6<
8512 THRESHOLD MV6< 2 .. 200 % 100 % Pickup Value of Measured Value
MV6<
Information List
No.
Information Type of
Informa-
tion
Comments
7960 Meas. Value1> OUT Measured Value MV1> picked up
7961 Meas. Value2< OUT Measured Value MV2< picked up
7962 Meas. Value3> OUT Measured Value MV3> picked up
7963 Meas. Value4< OUT Measured Value MV4< picked up
7964 Meas. Value5> OUT Measured Value MV5> picked up
7965 Meas. Value6< OUT Measured Value MV6< picked up
2.9.4
Functions
2.9 Threshold supervision
SIPROTEC 4, 7VE61 and 7VE63, Manual 103
C53000-G1176-C163-3, Edition 10.2017