EasyManua.ls Logo

Siemens SIPROTEC 4 7VE61 - Interface Modules

Siemens SIPROTEC 4 7VE61
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Pickup voltages of the BI6
Table 3-12 Jumper setting for the Pickup voltages (DC voltage) of the binary inputs BI6 on the C–I/O-8
board
Binary Inputs Jumper
19 V Threshold
1)
88 V Threshold
3)
176 V Threshold
3)
BI6 X21 1–2 2–3 3–4
1)
Factory settings for devices with rated power supply voltages of DC 24 V to 125 V
2)
Factory settings for devices with rated power supply voltages of DC 110 to 220 V and AC 115 V to 230 V
3)
Use only with control voltages 220 V or 250 V
Jumpers X71, X72 and X73 on the C–I/O-8 board serve to set the bus address. The jumpers must not be
changed. The following table lists the jumper presettings.
Bus address
Table 3-13 Jumper settings of the Bus address on the input/output board C-I/O-8
Jumper
Housing size
1
/
3
Housing size
1
/
2
X71 2–3 (L) 2–3 (L)
X72 2–3 (L) 2–3 (L)
X73 1–2 (H) 1–2 (H)
Interface Modules
Austausch von Schnittstellenmodulen
The interface modules are located on the C–CPU-2 board ((1) in Figure 3-2 and Figure 3-3). The following
figure shows the PCB with location of the modules.
Figure 3-2
3.1.2.4
Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC 4, 7VE61 and 7VE63, Manual 155
C53000-G1176-C163-3, Edition 10.2017

Table of Contents

Related product manuals