Input/Output Board C–I/O-8
[ein-ausgabebgr-c-io-8-190203-oz, 1, en_GB]
Figure 3-7
Input/output board C-I/O-8 with representation of the jumper settings required for the board
configuration
The selected control voltages of the binary input BI6 are checked according to Table 3-12. Jumper settings for
the contact mode of binary output BO5 are checked according to Table 3-11.
Figure 3-2 and Figure 3-3 illustrate the assignment of the binary inputs to the mounting location of the board.
Contact Mode
The contacts can be changed from normally open to normally closed with the output relay BO5. The following
table shows the setting of jumper X41 in dependance with the contact mode.
Table 3-11
Jumper settings for the Contact mode of the relays BO5 on the C–I/O-8 board
Jumper Open in quiescent state (NO) Closed in quiescent state (NC) Presetting
X41 1–2 2–3 1–2
Mounting and Commissioning
3.1 Mounting and Connections
154 SIPROTEC 4, 7VE61 and 7VE63, Manual
C53000-G1176-C163-3, Edition 10.2017