Characteristics
General Characteristics
Powerful 32-bit microprocessor system.
Complete digital measured value processing and control, from sampling and digitalizing of measured
values up to the switchon and switchoff decisions for power breakers and other switchgear.
Total electrical separation between the internal processing stages of the device and the external trans-
former, control and DC supply circuits of the system because of the design of the binary inputs, outputs,
and the DC converters.
Easy device operation via an integrated operator panel or by means of a connected personal computer
with the DIGSI operating program.
Continuous computation and display of measured quantities.
Storage of fault messages and instantaneous or rms values for fault recording.
Continuous monitoring of measured values as well as of the hardware and software of the device.
Communication with central control and memory storage equipment via serial interfaces, optionally via
data cable, modem, or optic fibre lines.
Battery-buffered real time clock that can be synchronized with an IRIG-B (or DCF77) signal, binary input
signal, or system interface command.
Statistics: Starting and trip commands from the device are counted.
Commissioning aids such as connection check, field rotation check, status display of all binary inputs and
outputs, and test measurement recording.
Synchrocheck, Dead Line/Bus
Settable minimum and maximum voltage
Verification of the synchronous conditions or the de-energized state is also possible before the manual
closing of the circuit breaker, with separate limit values
Fast measuring of voltage difference U
diff
, of the phase angle difference α
diff
and frequency difference f
diff
Measurement via transformer (integrated vector group adaptation)
Measuring voltages optionally for phase-phase or phase-earth.
Controlling Synchronous Networks
Fast measuring of the voltage difference U
diff
and of the phase angle difference α
diff
The operating mode is automatically activated (pre-settings), if the frequency difference is f
diff
≈ 0
Measurement via transformer (integrated vector group adaptation)
Measuring voltages optionally for phase-phase or phase-earth.
Controlling Asynchronous Networks
Fast measuring of the voltage difference U
diff
and of the frequency difference f
diff
;
Consideration of the angle difference with prediction of the point of synchronism
Measurement via transformer (integrated vector group adaptation)
Measuring voltages optionally for phase-phase or phase-earth.
1.3
Introduction
1.3 Characteristics
SIPROTEC 4, 7VE61 and 7VE63, Manual 21
C53000-G1176-C163-3, Edition 10.2017

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 4 7VE61 and is the answer not in the manual?

Siemens SIPROTEC 4 7VE61 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 4 7VE61
CategoryPower distribution unit
LanguageEnglish

Related product manuals