EasyManuals Logo

Siemens SIPROTEC 4 7VE61 User Manual

Siemens SIPROTEC 4 7VE61
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
Undervoltage Protection 27
Two-stage undervoltage measurement for one of the 6 input voltages of the device
Separated tripping delay time
Settable drop-off to pickup for both stages
Overvoltage Protection 59
Two-stage overvoltage measurement for one of the 6 input voltages of the device
Separated tripping delay time
Settable drop-off to pickup for both stages
Frequency Protection 81 O/U
Monitoring on undershooting (f<) and/or overshooting (f>) with 4 frequency limits and delay times that
are independently adjustable
Insensitive to harmonics and abrupt phase angle changes
Settable undervoltage threshold.
Frequency Change Protection
Monitors whether the frequency overshoots (df/dt>) and/or undershoots (-df/dt<) a set limit value, with 4
individually settable limit values or delay times
Variable measuring windows
Coupling to frequency protection pickup
Settable undervoltage threshold.
Vector Jump
Sensitive phase jump detection to be used for network disconnection.
Analog Outputs
Output of up to four analog operational measured values (depending on the variant ordered).
Threshold Value Monitoring
6 freely assignable messages for threshold monitoring
Implementation of fast monitoring tasks via CFC.
User-defined Functions
Internal and external signals can be logically combined to establish user-defined logic functions
All common logic functions (AND, OR, NOT, Exclusive OR, etc.)
Time delays and limit value interrogations
Processing of measured values, including zero suppression, adding a knee characteristic for a transducer
input, and live-zero monitoring.
Breaker Control
Circuit breakers can be opened and closed manually via programmable function keys, via the system
interface (e.g. by SICAM or LSA), or via the operating interface (using a PC with DIGSI)
Feedback information on circuit breakers states via the breaker auxiliary contacts
Plausibility monitoring of the circuit breaker position and monitoring of interlocking conditions for
switching operations.
Introduction
1.3 Characteristics
22 SIPROTEC 4, 7VE61 and 7VE63, Manual
C53000-G1176-C163-3, Edition 10.2017

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 4 7VE61 and is the answer not in the manual?

Siemens SIPROTEC 4 7VE61 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 4 7VE61
CategoryPower distribution unit
LanguageEnglish

Related product manuals