Rate-of-frequency-change protection
With the rate-of-frequency-change protection, frequency changes can be quickly detected. This allows a
prompt response to frequency dips or frequency rises. A trip command can be issued even before the pickup
threshold of the frequency protection (see Section 2.6 Frequency Protection) is reached.
Frequency changes occur for instance when there is an imbalance between the generated and the required
active power. They call for control measures on the one hand and for switching actions on the other hand.
These can be unburdening measures, such as network decoupling, or disconnection of loads (load shedding).
The sooner these measures are taken after malfunctioning, the more effective they will be.
The two main applications for this protection function are thus network decoupling and load shedding.
Functional Description
Measuring Principle
From the voltage at the selected input, the frequency is determined once per cycle over a measuring window
of 3 cycles, and a mean value of two consecutive frequency measurements is formed. The frequency differ-
ence is then determined over a settable time interval (default setting 5 cycles). The ratio between frequency
difference and time difference corresponds to the frequency change; it can be positive or negative. The meas-
urement is performed continuously (per cycle). Monitoring functions such as undervoltage monitoring, check
for phase angle jumps etc. to avoid overfunctioning.
Frequency Increase/ Decrease
The rate-of-frequency-change protection has four stages, from df1/dt to df4/dt. This allows the function to be
adapted variably to all power system conditions. The stages can be set to detect either frequency decreases (-
df/dt) or frequency increases (+df/dt). The -df/dt stage is only active for frequencies below the rated frequency,
or less if the underfrequency enabling is activated. Likewise, the df/dt stage is active for frequencies above the
rated frequency, or higher, if the overfrequency enabling is activated. The parameter setting decides for what
purpose the particular stage will be used.
To avoid a proliferation of setting parameters, the settable measuring window for the frequency difference
formation and the dropout difference are each valid for two stages.
Operating Ranges
The frequency can be determined as long as there is a sufficiently strong voltage at the selected input. If the
measurement voltage drops below a settable value U MIN, frequency protection is disabled because precise
frequency values can no longer be calculated from the signal.
Time Delays/Logic
Tripping can be delayed by a set time delay associated with each applied time stage. This is recommended for
monitoring of small gradients. When the time delay expires, a trip signal is generated. After pickup dropout
the tripping command is immediately reset, but not before the minimum command duration has expired.
Each of the four frequency change stages can be blocked individually by binary input. The undervoltage
blocking acts on all stages simultaneously.
2.7
2.7.1
Functions
2.7 Rate-of-frequency-change protection
92 SIPROTEC 4, 7VE61 and 7VE63, Manual
C53000-G1176-C163-3, Edition 10.2017

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 4 7VE61 and is the answer not in the manual?

Siemens SIPROTEC 4 7VE61 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 4 7VE61
CategoryPower distribution unit
LanguageEnglish

Related product manuals