Protocol-dependent Functions
Protocoll → IEC
60870-5-103
IEC 61850
Ethernet
(EN100)
Profibus DP DNP3.0 Modbus
ASCII/RTU
Additional
Service Inter-
face
(optional)
Function ↓
Operational meas-
ured values
Yes (fixed
values)
Yes Yes Yes Yes Yes
Metered values Yes Yes Yes Yes Yes Yes
Fault recording Yes Yes No Only via
additional
service inter-
face
No Only via
additional
service inter-
face
No Only via
additional
service inter-
face
Yes
Remote Relay
Setting
No Only via
additional
service inter-
face
No Only via
additional
service inter-
face
No Only via
additional
service inter-
face
No Only via
additional
service inter-
face
No Only via
additional
service inter-
face
Yes
User-defined alarms
and switching
objects
Yes Yes Yes Yes Yes Yes
Time synchroniza-
tion
Via protocol;
DCF77/IRIG B;
Interface;
Binary Input
Via protocol
(NTP);
DCF77/IRIG B;
Interface;
Binary Input
Via DCF77/IRIG
B; Interface;
Binary Input
Protocoll
Via protocol;
DCF77/IRIG B;
Interface;
Binary Input
Via DCF77/IRIG
B;
Interface;
Binary Input
Protocoll
—
Messages with time
stamp
Yes Yes Yes Yes Yes Yes
Commissioning aids
Alarm and measur-
edvalue blocking
Yes Yes No No No Yes
Test mode Yes Yes No No No Yes
Physical mode Asynchronous Synchronous Asynchronous Asynchronous Asynchronous —
Transfer mode Cyclically/
Event
Cyclically/
Event
Cyclically Cyclically/
Event
Cyclically —
Baud rate 4800 to 38400 up to
100 MBaud
up to 1,5
MBaud
4800 to 19200 2400 to 19200 4800 to
115200
Type RS232
RS485
Optical Fibre
Ethernet TP RS485
Optical Fibre
Double ring
RS485
Optical Fibre
RS485
Optical Fibre
RS232
RS485
D.7
Default Settings and Protocol-dependent Functions
D.7 Protocol-dependent Functions
SIPROTEC 4, 7VE61 and 7VE63, Manual 255
C53000-G1176-C163-3, Edition 10.2017