EasyManuals Logo

Siemens SIPROTEC 4 7VE61 User Manual

Siemens SIPROTEC 4 7VE61
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #181 background imageLoading...
Page #181 background image
[messspg-synchronisation-ueber-trafo-170403-kn, 1, en_GB]
Figure 3-23
Measuring voltages with synchronization via the transformer
The following checking steps have to be executed analogically to the previous checkings:
Set the tap changer of the transformator to the nominal position
Circuit breaker (b) is open and section switch (c) closed
Check the measured values on side U1 (U1, f1, phase rotation)
Check that the transformer differential protection is ready for operation
Close isolator (a1) and then close the circuit breaker (b)
Check the measured values on side U2 (U1, f1, phase rotation)
Compared the measured values on side 1 and on side 2:
Voltage equality U1 = U2
Frequency equality f1 = f2
The difference voltage dU is zero
The difference frequency df is zero
The difference angle dα is zero
i
i
NOTE
If dU and dα are unequal to zero, then wiring or setting error exist.
– Activate the tap changer and check again the measured values. The measured values on the side 2 have
to remain the same and all differential quantities must be equal to zero.
– After the test has been completed, you can reestablish the output switching condition.
Mounting and Commissioning
3.3 Commissioning
SIPROTEC 4, 7VE61 and 7VE63, Manual 181
C53000-G1176-C163-3, Edition 10.2017

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 4 7VE61 and is the answer not in the manual?

Siemens SIPROTEC 4 7VE61 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 4 7VE61
CategoryPower distribution unit
LanguageEnglish

Related product manuals