Loading...
No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
52 At Least 1 Protection
Funct. is Active (ProtAc-
tive)
Device IntS
P
O
N
OF
F
* * LED BO 70 18 1 Yes
55 Reset Device (Reset
Device)
Device OUT O
N
* * LED BO
56 Initial Start of Device
(Initial Start)
Device OUT O
N
* * LED BO 70 5 1 No
67 Resume (Resume) Device OUT O
N
* * LED BO
68 Clock Synchronization
Error (Clock SyncError)
Supervision OUT On
Of
f
* * LED BO
69 Daylight Saving Time
(DayLightSavTime)
Device OUT O
N
OF
F
* * LED BO
70 Setting calculation is
running (Settings Calc.)
Device OUT O
N
OF
F
* * LED BO 70 22 1 Yes
71 Settings Check (Settings
Check)
Device OUT * * * LED BO
72 Level-2 change (Level-2
change)
Device OUT O
N
OF
F
* * LED BO
73 Local setting change
(Local change)
Device OUT * * *
110 Event lost (Event Lost) Device OUT
_Ev
O
N
* * LED BO 13
5
13
0
1 No
113 Flag Lost (Flag Lost) Device OUT O
N
* m LED BO 13
5
13
6
1 Yes
125 Chatter ON (Chatter ON) Device OUT O
N
OF
F
* * LED BO 13
5
14
5
1 Yes
140 Error with a summary
alarm (Error Sum Alarm)
Supervision OUT On
Of
f
* * LED BO 70 47 1 Yes
160 Alarm Summary Event
(Alarm Sum Event)
Supervision OUT On
Of
f
* * LED BO 70 46 1 Yes
Functions, Settings, Information
E.3 Information List
SIPROTEC 4, 7VE61 and 7VE63, Manual 287
C53000-G1176-C163-3, Edition 10.2017

Table of Contents

Related product manuals