Siemens SIPROTEC 4 7VE61 - Page 304

Siemens SIPROTEC 4 7VE61
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
5590 >Failure: VT Uc (MCB
tripped) (>FAIL: VT Uc)
P.System
Data 1
SP On
Of
f
* * LED BI BO 41 85 1 Yes
5591 >Failure: VT Ud (MCB
tripped) (>FAIL: VT Ud)
P.System
Data 1
SP On
Of
f
* * LED BI BO 41 86 1 Yes
5592 >Failure: VT Ue (MCB
tripped) (>FAIL: VT Ue)
P.System
Data 1
SP On
Of
f
* * LED BI BO 41 87 1 Yes
5593 >Failure: VT Uf (MCB
tripped) (>FAIL: VT Uf)
P.System
Data 1
SP On
Of
f
* * LED BI BO 41 88 1 Yes
6503 >BLOCK undervoltage
protection (>BLOCK U/V)
Under-
voltage
SP * * * LED BI BO
6506 >BLOCK Undervoltage
protection U< (>BLOCK
U<)
Under-
voltage
SP On
Of
f
* * LED BI BO 74 6 1 Yes
6508 >BLOCK Undervoltage
protection U<< (>BLOCK
U<<)
Under-
voltage
SP On
Of
f
* * LED BI BO 74 8 1 Yes
6513 >BLOCK overvoltage
protection (>BLOCK O/V)
Overvoltage SP * * * LED BI BO
6516 >BLOCK overvoltage
protection U> (>BLOCK
U>)
Overvoltage SP On
Of
f
* * LED BI BO 74 20 1 Yes
6517 >BLOCK overvoltage
protection U>> (>BLOCK
U>>)
Overvoltage SP On
Of
f
* * LED BI BO 74 21 1 Yes
6530 Undervoltage protection
switched OFF (Undervolt.
OFF)
Under-
voltage
OUT On
Of
f
* * LED BO 74 30 1 Yes
6531 Undervoltage protection
is BLOCKED (Undervolt.
BLK)
Under-
voltage
OUT On
Of
f
On
Off
* LED BO 74 31 1 Yes
6532 Undervoltage protection
is ACTIVE (Undervolt.
ACT)
Under-
voltage
OUT On
Of
f
* * LED BO 74 32 1 Yes
6533 Undervoltage U< picked
up (U< picked up)
Under-
voltage
OUT * On
Off
* LED BO 74 33 2 Yes
6537 Undervoltage U<< picked
up (U<< picked up)
Under-
voltage
OUT * On
Off
* LED BO 74 37 2 Yes
6539 Undervoltage U< TRIP (U<
TRIP)
Under-
voltage
OUT * On * LED BO 74 39 2 Yes
Functions, Settings, Information
E.3 Information List
304 SIPROTEC 4, 7VE61 and 7VE63, Manual
C53000-G1176-C163-3, Edition 10.2017