Figure 2-29
Example of measurement via transformer
In the 3 function groups values are taken from the following table and entered for the adaptation factor 6121
Balancing U1/U2. Via binary input
>Sy1 activ
to
>Sy8 wirks
the synchronizing function suitable for
the current transformer tap can be selected. This can occur directly via binary input or be derived from the
CFC.
Table 2-4
Possible Transformator Settings
Transformer
Tap
Primary rated voltage U2 Balancing Factor U1/U2
1 36.0 kV 1.06
2 37.0 kV 1.03
3 38.0 kV 1.00
The parameter 6122 ANGLE ADJUSTM. is used to correct any phase angle errors between the voltage trans-
formers in degree steps. A possible correction value should be derived during commissioning.
Using the setting parameters Balancing U1/U2 and ANGLE ADJUSTM. system versions can be managed
where voltage transformers are connected differently or different voltage transformers are used on side 1 and
side 2. The setting can be explained by two examples. In Figure 2-30 the two-pole isolated voltage trans-
formers are connected to different phase-to-phase voltages. Both primary and secondary voltages are equal.
Functions
2.2 Paralleling Functions
SIPROTEC 4, 7VE61 and 7VE63, Manual 65