EasyManua.ls Logo

Siemens SIRIUS 3RK3 - Page 316

Siemens SIRIUS 3RK3
402 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Messages for protective door
The following table shows the messages with the associated byte arrangement in the element
data block of the "protective door" function element.
Byte po‐
sition
Message Meaning Element status Cyclic data
6
0
Startup test required This message is set in a parame‐
terized startup test on each re‐
start and each time the substitute
value is changed to a real value
until the connected sensor is ac‐
tuated at least once.
SVW SVW
6
1
Sequence condition not
ful󹪝lled
The sequence condition was not
ful󹪝lled in accordance with the
parameter assignment.
Logic error SF
6
2
Discrepancy condition
violated
is set if:
After the discrepancy time
has elapsed, the signal states
at the inputs monitored are
di󹪜erent
The signal states of the inputs
monitored had not all previ‐
ously been reset simultane‐
ously to the value "0" when
they are set to "1"
Logic error SF
6
3
Safety sensor triggered The safety sensor has been actu‐
ated.
SVW SVW
6
4
... 6
7
Reserved=0
7
0
Cross-circuit at input 1 A cross-circuit was detected at in‐
put 1.
Wiring error SF
7
1
... 7
3
Reserved=0
7
4
Cross-circuit at input 2 A cross-circuit was detected at in‐
put 2.
Wiring error SF
7
5
... 7
7
Reserved=0
8
0
Start signal duration in‐
valid
Only with start type "Monitored
start":
The start signal time monitoring
element detected a violation.
Diagnostics / service
7.6 Diagnosis using AS-Interface (CTT2 protocol)
SIRIUS 3RK3 Modular Safety System
316 Equipment Manual, 07/2020, NEB926253002000/RS-AC/006

Table of Contents

Other manuals for Siemens SIRIUS 3RK3

Related product manuals