EasyManua.ls Logo

Siemens SITRANS FUE1010 IP65 NEMA 4X - Page 193

Siemens SITRANS FUE1010 IP65 NEMA 4X
296 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
A.3 I/O Connections and Wiring
FUE1010 IP65 NEMA 4X
Operating Instructions, 12/2014, A5E03086491-AC
191
Table A- 19 Input/Output Wiring TB5 7ME39404SB00 - Analog Input Module (2 Chan/Dual Path)
Pin
Function
Use
Description
Behavior
Load
Wiring/Cable
TB5-1
AUX. 1 IN
Iin1 Input
Analog current
input refer-
enced to meter
ground
4 to 20 mA 200 Ω AWG. 14-24 /
100 ft. max. w/o
factory approval
TB5-2
AUX. 1 COM
Iin1 Common
TB5-3
AUX. 2 IN
Iin2 Input
TB5-4 AUX. 2 COM Iin2 Common
Net load is 335 ohms when safety barriers are used.
Black
Terminal Board 1
Orange
Terminal Board 2
Brown
Terminal Board 5
Red
To Sensors
Blue
Terminal Board 4
Terminal Board 3
Figure A-5 Temperature Sensor Inputs

Table of Contents