Chapter 4 Servicing Motherboard Components 4-39
11. Power on the server.
See Section 6.4, “Powering On the Server” on page 6-6.
A message appears stating that the BMC was not found.
The server takes up to three minutes to boot.
12. Press F2 to enter system BIOS and verify that the Flash device is in the boot
order.
13. After the flash device has booted, run the following command:
socflash.exe SP binary backup file
For example:
socflash.exe s92v092.bin backup.bin
14. After a successful flash, remove the AC power.
See Section 2.4, “Powering Off the Server” on page 2-3.
15. Remove the jumper.
16. Remove the flash drive from the USB port.
17. Replace PCI cards from Riser 1.
See “To Install PCIe Cards” on page 4-19.
18. Reinstall the top cover.
See Section 6.1, “Installing the Top Cover” on page 6-2.
19. Slide the server into the rack.
See Section 6.3, “Returning the Server to the Normal Rack Position” on page 6-5.
20. Reconnect the power cord (or cords) to the power supply (or supplies).
Verify that the AC Present LED is lit.
See Section 6.4, “Powering On the Server” on page 6-6.
21. Power on the server.
See Section 6.4, “Powering On the Server” on page 6-6.
22. Confirm that the SP is listed in the BIOS settings under Server/AST2000 LAN
Configuration.