F73 – Alarm Control / Status
F73<SP>THRESHOLD<SEP><nanoseconds><CR>
The XL-GPS will set the new time error threshold and returns the following string if the
command is successful.
OK<CR><LF>
Set or query Timeout Delay using the TIMEOUT command. To query the current setting,
enter:
F73<SP>TIMEOUT<CR><LF>
The XL-GPS responds:
F73<SP>TIMEOUT<SEP><seconds><SP>s<CR><LF>
where <seconds> is the timeout in seconds, between 0 and 86400.
To set Timeout Delay, enter a command string in the following format:
F73<SP>TIMEOUT<SEP><seconds><CR><LF>
The XL-GPS will set the new timeout delay and responds:
OK<CR><LF>
Led blinking can be ENABLED or DISABLED using the BLINK command. To enable LED
blinking, enter:
F73<SP>BLINK<SEP>ENABLE<CR>
The XL-GPS responds:
OK<CR><LF>
To disable LED blinking, enter:
F73<SP>BLINK<SEP>DISABLE<CR>
The XL-GPS responds:
OK<CR><LF>
Use the SUPPRESS command to suppress all F73 faults from triggering alarms for a
specified duration after the XL-GPS power is turned on. To check the SUPPRESS status,
enter:
F73<SP>SUPPRESS<CR>
The XL-GPS responds in the following format:
098-00116-000 Rev. A............................... Page 103 of 221

Table of Contents

Other manuals for Symmetricom XL-GPS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Symmetricom XL-GPS and is the answer not in the manual?

Symmetricom XL-GPS Specifications

General IconGeneral
BrandSymmetricom
ModelXL-GPS
CategoryReceiver
LanguageEnglish

Related product manuals