EasyManuals Logo

Toshiba TOSVERT VF-AS3 User Manual

Toshiba TOSVERT VF-AS3
622 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #100 background imageLoading...
Page #100 background image
E6582062
2. Installation and wiring 2-66
2
9
Circuit diagram 1 is an example in which the standby function is assigned to the terminal [S2]. This
circuit can be applied to a machine that mainly operates horizontally. Set the terminal [S2] to "Open"
to turn off output of the inverter and have the motor in coasting state. Then. operate the brake. If the
brake is operated with inverter output, the inverter may trip due to bound current. Note that when it is
applied to a machine with vertical movements, the motor may fall when it is in coasting state.
Circuit diagram 2 is an example in which low-speed signals are assigned to the terminals [R1A]-
[R1C]. This circuit can be applied also to a machine with vertical movements. At the time of start,
output is made from the inverter while the brake is operating. When the output frequency reaches
<F100: Low-speed signal output frequency>, the brake is released by the signal output from the
terminals [R1A]-[R1C]. When the machine stops, the inverter comes to deceleration stop. When the
output frequency decreases under <F100>, the output signal from the terminals [R1A]-[R1C]
becomes off and the brake operates.
Measures to protect motors against surge voltages
In a system in which a 480 V class inverter is used to control the operation of a motor, very high
surge voltages may be produced depending on the wire length, wire routing and types of wires used.
If such surge voltages are applied repeatedly for a long time, it may cause deterioration of insulation
of motor coils.
Here are some examples of measures against surge voltages.
Decrease <F300: Carrier frequency> of the inverter.
Use a motor with high insulation strength.
Insert an AC reactor or a motor-end surge voltage suppression filter between the inverter and the
motor. Refer to [10. 3. 5].
2. 4. 2 Inverters
For the inverters to be used, pay attention to the following items.
Inverter capacity
Do not operate a motor whose capacity is larger than the inverter (e.g. a 45 kW motor with a 30 kW
inverter), no matter how light the load is. Current ripple will raise the output peak current, making it
easier to set off the overcurrent trip.
Power factor correction capacitor
Power factor correction capacitors cannot be installed on the output side of the inverter. To operate
a motor with a power factor correction capacitor attached, remove the capacitor. Otherwise, it will
cause an inverter malfunction and capacitor destruction.
Inverter
V/T2
U/T1
W/T3
M
Remove power factor correction
capacitors and surge absorber.
Power factor correction capacitor

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m

Related product manuals