E6582062
6. [Advanced] How to use parameters 6-32
4
4
6
9
6. 7. 1 Setting the starting frequency and the end
frequency
<F240: Start frequency>
<F243: End frequency>
Function
The frequency set for <F240: Start frequency> is instantly output at startup.
This parameter is used when the delayed response of starting torque caused by the acceleration/
deceleration time affects the frequency.
When the output frequency is decreased to the frequency set for <F243: End frequency>, the
frequency instantly becomes 0 Hz when stopping.
Parameter setting
Setting method
Use the parameters when the delayed response of starting torque caused by the acceleration/
deceleration time affects the frequency. For the setting values, 0.1-3.0 Hz (5 Hz or less) is
recommended. Overcurrent can be reduced by setting the value to the motor rated slippage or less.
Set the values so that <F240: Start frequency> is higher than <F243: End frequency>.
When <F240> is lower than <F243>, no operation is performed by any frequency command lower
than <F243>.
6. 7 Setting the start and end frequencies
Title Parameter name Adjustment range Unit Default setting
F240 Start frequency 0.0-10.0 Hz 0.1
F243 End frequency 0.0-30.0 Hz 0.0
0.0HzSTOP
13:00
F240 : Start frequency
Min: 0.0 Max: 10.0
X1000 X100 X10 X1
Hz
0.1
Output frequency (Hz)
<F240: Start frequency>
<F243: End frequency>
Time (s)
0

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m

Related product manuals