E6582062
10. Selection and installation of peripheral devices 10-4
9
10
According to the table [10. 2. 1], select an appropriate wiring device depending on the voltage class and
capacity of the inverter.
10. 2. 1 Selection table of a wiring device
Select a wiring device depending on the inverter type and input current in the table next.
Wiring devices for HD rating
10. 2 Selection of a wiring device
Voltage
class
Applicable
motor (kW)
Inverter type-form Input current (A)
Rated current (A)
Molded-case circuit
breaker (MCCB)
Earth leakage circuit
breaker (ELCB)
Magnetic contactor
(MC)
3-phase
240 V
0.4 VFAS3- 2004P 1.7
3 20
0.75 2007P 3.3
5 20
1.5 2015P 6.0
10 20
2.2 2022P 9.0
15 20
4.0 2037P 15.1
20 20
5.5 2055P 20.1
30 32
7.5 2075P 27.3
40 32
11 2110P 40.0
50 50
15 2150P 53.2
75 60
18.5 2185P 64.8
100 80
22 2220P 78.3
100 80
30 2300P 104.7
150 150
37 2370P 128.4
175 200
45 2450P 157.6
200 260
55 2550P 189.0
250 260

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m

Related product manuals