6. [Advanced] How to use parameters 6-164
4
4
6
9
Lock or unlock the key operation of the operation panel and parameter setting.
Also, set the display functions of the operation panel.
6. 34. 1 Lockout key operation and parameter setting
<F700: Parameter reading&writing access lockout>
<F730: Panel frequency setting lockout>
<F731: Operation after disconnection detection during
panel run>
<F732: Panel Hand/Auto function lockout>
<F733: Panel Run lockout>
<F734: Panel emergency off lockout>
<F735: Panel reset lockout>
<F736: CMOd/FMOd change lockout during run>
<F737: Panel keys lockout>
<F738: Password setting>
<F739: Password verification>
â–  Function
These parameters allow you to locked or unlocked operation on the operation panel and the change
of parameters. Using these parameters, you can also lock various key operations to prevent
malfunction.
Lock parameters with a password to prevent configuration.
â–  Parameter setting
6. 34 Setting functions of operation panel
Title Parameter name Adjustment range Default setting
F700 Parameter
reading&writing access
lockout
*1
0: Unlocked
1: Writing locked (Operation panel, Extension
panel)
2: Writing locked (1+RS485)
3: Reading&Writing locked (Operation panel,
Extension panel)
4: Reading&Writing locked (3+RS485)
0
F730 Panel frequency setting
lockout
0: Unlocked
1: Locked
2: Unlocked after press OK
2
F731 Operation after
disconnection detection
during panel run
*2
1: Continue running
2, 3: -
4: Trip
4
F732 Panel Hand/Auto
function lockout
*3
0: Unlocked
1: Locked
1
F733 Panel Run lockout 0: Unlocked
1: Locked
0
F734 Panel emergency off
lockout
0: Unlocked
1: Locked
0
1: Writing locked (Op & Ext panel)
2: Writing locked (1+RS485)
3: Read&Write locked (panel)
4: Read&Write locked (3+RS485)
0.0HzSTOP
14:12
0: Unlocked
F700 : Parameter read&write lock

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-AS3
CategoryInverter
LanguageEnglish

Related product manuals