6-165 6. [Advanced] How to use parameters
3
4
6
9
Selecting a setting value
In [Standard mode], if you lock the frequency setting on the operation panel (<FC>, <FPId>, Preset
speed), set <F730: Panel frequency setting lockout> to "1".
You cannot lock the setting with <F700>.
Setting/clearing method of password when it is required for protection
1) Password setting method
Parameters other than <F700>, <F738>, and <F739> cannot be changed when <F700> is set
to "1" to "4".
When <F738> or <F739> is "0", a password has not been set. You can set a new password.
When <F738> or <F739> is "9999", a password has already been set.
If not set, select and register a number from "1" to "9998" for <F738> as a password. Do not
forget your password as it is required to release the lock.
F735 Panel reset lockout 0: Unlocked
1: Locked
0
F736 CMOd/FMOd change
lockout during run
0: Unlocked
1: Locked
1
F737
Panel keys lockout
*4
0: Unlocked
1: Locked
2: Locked only extension panel
3: Locked only operation panel
0
F738
Password setting
*5
0: Disabled
1 - 9998
9999: Password was set
0
F739 Password verification 0: non-setting
1 - 9998
9999: Password was set
0
*1 The setting of <F700>="2" and "4" is valid after reset (turning off power).
*2 Enabled when run command is input from the operation panel.
*3 <F732> is only for extended LED panel. <F750> is for LCD panel.
*4 After setting <F737>. turn on the power again. The setting is valid after the power is turned on
again.
*5 The setting of <738>="9999" is valid after reset (turning off power).
Important
The lock cannot be released if you forget the password. Do not forget this password as we
cannot retrieve it.
Title Parameter name Adjustment range Default setting

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m