E6582062
6. [Advanced] How to use parameters 6-108
4
4
6
9
6. 27. 1 Setting Acc/Dec patterns
<F502: Acc/Dec pattern 1>
<F506: S-Pattern range at Acc start>
<F507: S-Pattern range at Acc completion>
<F508: S-Pattern range at Dec completion>
<F509: S-Pattern range at Dec start>
Function
You can select acceleration/deceleration patterns suitable for the purpose.
Parameter setting
How to select the setting value for <F502>
0: Linear pattern
This is linear acceleration and deceleration, and is a normal Acc/Dec pattern.
Normally, you can use this setting for operation.
6. 27 Switching multiple acceleration/
deceleration
Title Parameter name Adjustment range Unit Default setting
F502 Acc/Dec pattern 1 0: Linear
1: S-Pattern 1
2: S-Pattern 2
0
F506 S-Pattern range at Acc
start
0-50 % 10
F507 S-Pattern range at Acc
completion
0-50 % 10
F508 S-Pattern range at Dec
completion
0-50 % 10
F509 S-Pattern range at Dec
start
0-50 % 10
1: S-Pattern 1
2: S-Pattern 2
0.0HzSTOP
13:49
0: Linear
F502 : Acc/Dec pattern 1

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m

Related product manuals