9
<F262: Panel jog run>
<F260: Jog frequency>
<F261: Jog stop select>
â– Function
Jog run represents inching the motor.
When you input a jog run signal, the inverter immediately outputs a jog run frequency regardless of
the set acceleration time.
You can start/stop jog run even on the operation panel.
â– Parameter setting
â– Setting example
Assign "18: jog run" to the unused input terminal.
While that input terminal is turned ON, the inverter can perform jog run.
To use only the panel jog run, you should not assign it to the input terminal.
Example) When it is assigned to the terminal [RES]: <F113: Terminal RES function 1> = "18"
The inverter outputs a low-speed detection signal but does not output an output frequency
attainment signal during jog run. Also, PID control is disabled.
<Example of jog run>
Terminal [RES] (JOG): ON + terminal [F]: Forward jog run when the terminal is turned ON
Terminal [RES] (JOG): ON + terminal [R]: Reverse jog run when the terminal is turned ON
(Frequency command + terminal [F]: Forward run when the terminal is turned ON, terminal [R]:
Reverse run when the terminal is turned ON)
6. 10 Jog run
Title Parameter name Adjustment range Unit Default setting
F262 Panel jog run 0: Disabled
1: Enabled
0
F260 Jog frequency F240 - 20.0 Hz 5.0
F261 Jog stop select 0: Deceleration stop
1: Coast stop
2: DC braking stop
0
0: Disabled
1: Enabled
0.0HzSTOP
13:11
F262 : Panel jog operation