9
<F650: Forced run>
â– Function
With the forced run control, the motor runs at the specified speed in an emergency.
â– Parameter setting
â– Setting the parameters and input terminal
Set <F650: forced run> = "1: Enabled"
Set any of the function to the unused input terminal. For details, refer to [7. 2. 1].
You can perform the forced run or fire speed run with the setting of <F650> = "1" and an assigned
input terminal is ON.
 "56: Forced run"
• Once the input signal is ON, it is self-retained. The motor runs at the frequency set by
<F294>.
• In case of a slight failure, the motor performs the forced run, in which the operation is continued.
 "58: Fire speed run"
• Once the input signal is ON, it is self-retained. The motor performs the fire speed run at the
frequency set by <F294>.
In both cases, to stop the running, the power circuit needs to be turned off.
During the forced run and the fire speed run, "FIrE" is displayed.
â– Signal output of forced run
Assign any of these to the unused output terminal. For details, refer to [7. 2. 2].
 "138: During forced run"
 "140: During fire speed run"
6. 31 Forced run control in emergency
Title Parameter name Adjustment range Unit Default setting
F650 Forced run 0: Disabled
1: Enabled
0
F294 Preset speed 15 / Forced
run speed
LL - UL Hz 0.0
0.0HzSTOP
14:07
F650 : Forced run
0: Disabled
1: Enabled