E6582062
6. [Advanced] How to use parameters 6-42
4
4
6
9
<F256: Run sleep detection time>
<F259: Run sleep detection time at startup>
<F391: Sleep detection hysteresis>
<F392: Wakeup deviation>
<F393: Wakeup feedback>
■ Function
This function is used to automatically decelerate and stop the inverter in the following case: the
inverter continues to run at the frequency set with <LL: Lower limit frequency>, which has a low
workload, for the period specified in <F256: Run sleep detection time> for energy-saving, etc. (sleep
function).
The LCD screen displays "LStP" during sleep.
■ Parameter setting
■ Guideline for the setting
This function is used to automatically decelerate and stop the inverter when it continues to run at the
frequency set with <LL: Low limit frequency>.
Set a duration with <F256: Sleep detection time>.
6. 9 Automatic stop when run continues at the
lower limit frequency (sleep function)
Title Parameter name Adjustment range Unit Default setting
F256 Run sleep detection time 0.0: Disabled
0.1 - 600.0
s0.0
F259 Run sleep detection time
at startup
0.0: Disabled
0.1 - 600.0
s0.0
F391 Sleep detection
hysteresis
0.0 - UL Hz 0.0
F392 Wakeup deviation 0.0 - UL Hz 0.0
F393 Wakeup feedback 0.0 - UL Hz 0.2
0.0HzSTOP
13:10
F256 : Sleep detection time
Min: 0.0 Max: 600.0
X1000 X100 X10 X1
0.0
s
Run signal [F] or [R]
ON
OFF
Output frequency (Hz)
Time (s)
<F259><F259> <F256><F256>
<LL>
<LL> + <F391>