E6582062
9-11 9. Measures to satisfy standards
3
9
The input withstand rating is obtained with heat calculation. If the fuse is installed to a circuit with
larger input withstand rating, a reactor should be installed so that the input withstand rating should be
reduced below this level.
Output interrupt rating varies depending on the type of integral solid state short circuit. Install the fuse
according to the NEC standard, local standard and type of installation.
Use a fuse of Cooper Bussmann or Mersen.
Be sure to use rod crimp-style terminals for the grounding terminals of the heat sink and metal plate
of the inverter.
9. 2. 4 Overload protection
The overload protection levels are below,
HD rating: 150%-1minute, 180%-2s (Frame size A1~A6)
150%-1minute, 165%-2s (Frame size A7, A8)
ND rating: 120%-1minute, 135%-2s (All frame sizes)
For the rated current, refer to the name plate.
9. 2. 5 Motor thermal protection
To use the electronic thermal function of this inverter for motor thermal protection, set parameters
according to the motor specifications applied. For details, refer to [5. 2. 5].
When operating multiple motors with one inverter, install overload relay for each motor.
9. 2. 6 Motor integrated PTC thermal protection
For details, refer to [6. 30. 19].
9. 2. 7 Other
Contact your Toshiba distributer or Toshiba sales representative (see the back cover of this manual), if
you need the hard copy (paper) of CD-ROM.
For details, refer to “VF-AS3 Safety function manual" (E6582068).
9. 3 Compliance with safety standards

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m

Related product manuals