E6582062
2-69 2. Installation and wiring
2
3
9
10
Influence of leakage current across lines (in case of thermal relays)
The high frequency component of current leaking into electrostatic capacity between inverter output
wires will increase the effective current values and make externally connected thermal relays operate
unnecessarily. When the wires are long (50 m or more) or in case of models with motors of low rated
current (several A (ampere) or less), especially the 480 V class low capacity (4.0 kW or less, 5.5 kW
or less with ND) models, it will be easy for the external thermal relay to activate unnecessarily,
because the ratio of leakage current against the motor rating will increase.
Here are some examples of measures against leakage current across lines.
Use the electronic thermal of the inverter.
The setting of the electronic thermal is done with <tHrA: Motor overload protection current 1>. For
details, refer to [5. 2. 5].
Decrease <F300: Carrier frequency>.
However, note that the motor magnetic noise is increased.
For details, refer to [6. 14].
Install 0.1 to 0.5μF - 1000 V film capacitor to the input/output terminals of each phase in the
thermal relay.
Inverter
Power
supply
Thermal relay
M
A
CT
Leakage current path across wires
Thermal relay
Inverter
M
U/T 1
V/T 2
W/T 3

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m

Related product manuals