EasyManuals Logo

Toshiba TOSVERT VF-AS3 User Manual

Toshiba TOSVERT VF-AS3
622 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #205 background imageLoading...
Page #205 background image
E6582062
5-39 5. [Fundamental operation] How to use parameters
3
4
5
9
To increase the torque at low speeds, increase the setting value of <vb: Manual torque boost 1>. For
details, refer to [5. 3. 6].
1: Variable torque
This is applied to loads such as fans, pumps and blowers in which the torque is proportional to the
square of load motor speed.
2: Automatic torque boost
The load current in the speed range from startup to base frequency is detected and the output
voltage (torque boost) from the inverter is automatically adjusted. This gives steady torque for stable
operation.
It is applied to loads that require torque.
Operation may become unstable depending on loads. In this case, set <Pt> = "0: V/f constant" and
increase the value of <vb: Manual torque boost 1>.
Setting of motor parameters
When <Pt> is "2", setting of motor parameters is required.
Output frequency (Hz)
Output voltage (V)
0
<vLv: Base frequency voltage 1>
<vL: Base frequency 1>
<vb> (%)
00
Output frequency (Hz)
Output voltage (V)
<vLv: Base frequency voltage 1>
<vL: Base frequency 1>
<vb> (%)
0
: Automatically
adjusted to torque
boost value
Output frequency (Hz)
Output voltage (V)
<vLv: Base frequency voltage 1>
<vL: Base frequency 1>

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m

Related product manuals