EasyManuals Logo

Toshiba TOSVERT VF-AS3 User Manual

Toshiba TOSVERT VF-AS3
622 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #297 background imageLoading...
Page #297 background image
E6582062
6-55 6. [Advanced] How to use parameters
3
4
6
9
Selecting the setting value
When using the regenerative power ride-through: <F302: Regenerative power ride-through> = "1"
Set <F302> to "1: Regenerative power ride-through".
A motor is controlled according to <F313: Ridethrough time>.
Note that the available time to continue the operation varies by the mechanical inertia or load
condition. The motor may enter the coasting state depending on the load condition.
Set the operation level of regenerative power ride-through with <F629: Regenerative power ride-
through level>.
100% reference is 200 V (240V class), 400 V (480V class)
Set it to a value equal to <F625: Undervoltage detection level> decreased by 5%, or more. Or, set
it to a value equal to <F629: Regenerative power ridethrough level> increased by 5%, If the setting
is inappropriate, the regenerative power ride-through control time may become too short. This is
not required when <F625> is "80: Auto".
When <F303: Retry> is used together, you can restart a motor without stopping it in case a trip
occurs.
To restart a motor smoothly after restoration of power, use <F301: Auto-restart> together.
This does not function during torque control.
When using the deceleration stop at power failure: <F302: Regenerative power ride-through> = "2"
Set <F302> to "2: Deceleration stop at power failure".
A motor makes a deceleration stop according to <F310: Dec time at power failure>. The
deceleration time is from <FH: Maximum frequency> to 0 Hz. With <F302> set to "2", <F310>
cannot be written during run.
Set the operation level of deceleration stop at power failure with <F626: Overvoltage limit
operation level>. 100% reference is 200 V (240V class), 400 V (480V class).
When the voltage falls to <F625: Undervoltage detection level> or less during a deceleration stop
due to power failure, the motor will enter the coasting state.
"StOP" is displayed on the operation panel during the stop. The stop state is kept until the run
command is turned OFF.
This does not function during torque control.
When using the synchronized Acc/Dec: <F302: Regenerative power ride-through> = "3" or "4"
Set <F302> to "3: Synchronized Acc/Dec (TB)" or "4: Synchronized Acc/Dec (TB + power failure)".
The deceleration time set by <F317: Synchronized stop time> and acceleration time set by <F318:
Synchronized reach time> are used.
This does not function during torque control.
The jog run is disabled while this function is set.
F313 Ridethrough time 0.0: Continuous
0.1 - 320.0 s
2.0
F317 Synchronized stop time 0.0 - 6000 s 2.0
F318 Synchronized reach time 0.0 - 6000 s 2.0
F625 Undervoltage detection
level
50 - 79
80: Auto
%80
F629 Regenerative power
ridethrough level
55 - 100 % 75
Title Parameter name Adjustment range Unit Default setting

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m

Related product manuals