E6582062
6-91 6. [Advanced] How to use parameters
3
4
6
9
Due to residual voltage, auto-tuning may not be properly performed immediately after
running motor is stopped.
There would be almost no rotation of the motor during offline auto-tuning, but you must keep
in mind that voltage is still applied during this time.
During auto-offline tuning, "Atn" will be displayed on the LCD screen.
Offline auto-tuning takes a few seconds. If any failure is found, tripping will occur with auto-
tuning error "Etn1" or "Etn2", and motor parameters will not be set.
Offline auto-tuning cannot be performed on special motors. Calculate the motor parameters
using "Setting method 2".
If offline auto-tuning cannot be performed or auto-tuning error "Etn1" or "Etn2" occurs, set
manually using "Setting method 3".
Setting method 2: Make auto-tuning of motor parameter after automatic setting.
Set PM motor control and then perform motor parameters auto calculation.
Check the motor name plate and set the following parameters first.
<vL: Base frequency 1> (Rated frequency)
<vLv: Base frequency voltage 1> (Rated voltage)
<F405: Motor rated capacity>
<F415: Motor rated current>
<F417: Motor rated speed>
Next, set <Pt: V/f Pattern> to "6: PM motor control". For details of setting methods, refer to [5. 3. 4].
Then, select <F400> = "4: Motor parameters auto calculation (0 after execution)" and perform <vLv:
Base frequency voltage> auto calculation.
This setting can be made without connecting the motor since it only calculates.
After automatic setting of motor parameter with <F400> = "4", be sure to set <F400> to "2: Auto-
tuning at run command (0 after execution)" and execute an auto-tuning.
Since calculation is performed based on general trend, the calculation results may not be correct. In
this case, set the parameter manually.
Setting method 3: Manually setting motor parameter
Set <Pt: V/f Pattern> to "6: PM motor control" and set the motor parameter manually.
If tuning error "Etn1" is displayed during auto-tuning setting or when you want to improve PM motor
control characteristics, set motor parameters individually. For details of setting methods, refer to [5.
3. 4].
4) Parameter setting
Title Parameter name Adjustment range Unit Default setting
F402 Automatic torque boost 0.1 - 30.00 %
*1
F405 Motor rated capacity 0.01 - 315.0 kW
*1
F415 Motor rated current
*1
A
*1 *1
F417 Motor rated speed 100 - 64000
min
-1 *2
F459 Load inertia ratio 0.1 - 100.0 Times 1.0
F460 Speed control response
1
0.0 - 25.0 - 0.0