E6582062
2. Installation and wiring 2-32
2
9
[Standard connection diagram - Sink]
This diagram shows an example of a standard connection for 240 V class, 0.4 to 37kW and 480 V
class, 0.4 to 75kW (frame size A1 to A5).
*1 EMC filter is built in 480 V class.
*2 External braking resistor (option).
*3 To input DC power, connect the inverter between the terminals [PA/+] and [PC/-].
*4 If your inverter is 240 V with 11kW or more, or 480 V with 22kW or more. when using it with a DC power supply, a circuit to suppress an inrush cur-
rent is required. For detail, refer to application manual "DC power supply connect to inverter" (E6582156).
*5 For the switch function, refer to [2. 3. 5].
*6 To supply control power from an external power supply for backing up the control power supplied from the inverter, an optional control power supply
unit (CPS002Z) is required. In this case, it is used in conjunction with the inverter internal power supply.
Set <F647: Control power option failure detection> to back up the control power supply.
For details, refer to [6. 30. 20].
*7 The reset signal is activated by ONOFF trigger input.
*8 Connect to power to comply with OVC2 (Over Voltage Category 2). Isolation transformer is necessary when connecting to power supply (OVC3).
+SU
CC
FLA
FLB
FLC
R1A/R2A
R1C/R2C
FM
AM CC RX II RR PP
STOB
STOA
PLC
PLC
SINK
SOURCE
SW1
*5
*6
*1
*2
*3
*4
*6
FP
Pulse counter
CC
S5
S4
S3
S2
S1
RES
R
F
Fwd run
Rev run
Reset 1
Preset speed switching 1
Preset speed switching 2
Preset speed switching 3
Preset speed switching 4
Preset speed switching 5
Common
*7
Digital input
P24
Power supply
240 V class:
0.4 - 37 kW Three-phase 200 - 240 V-50/60 Hz
480 V class:
0.4 - 75kW Three-phase 380 - 480 V-50/60 Hz
Control
circuit
DC/DC
Power
circuit
Noise
filter
DC reactor
Voltage signal: -10 to +10 V
Ammeter or voltmeter
Current signal: 4(0) to 20 mA
R/L1
U/T1
V/T2
M
Motor
W/T3
PA/+
+DC -DC
PB PC/-
S/L2
T/L3
MCCB
or
ELCB
Default
setting
(Or, input voltage signal of 0 - 10 V between the terminals [RR] and [CC])
External potentiometer
Frequency
meter
Ammeter
*8