E6581158
F-17
6
Q Parameter setting
Title Function Adjustment range Default setting
HOQF
Frequency setting mode selection 1
0: Built-in potentiometer
1: VIA/II
2: VIB
3: Operation panel
4: Serial communication
5: UP/DOWN from external
contact
6: VIA + VIB (Override)
0
H
Frequency priority selection
0: HOQFҏ(Switchable to H
by the input terminal)
1: HOQF (H for output fre-
quencies equal to or lower than
1.0 Hz)
0
C
Speed setting mode selection 2
0: Built-in potentiometer
1: VIA
2: VIB
3: Operation panel
4: Serial communication
5: UP/DOWN from external
contact
6: VIA + VIB (Override)
1
1) External switching (Input terminal function 38 : FCHG enabled)
Frequency priority selection parameter H =
Switching between the command specified with HOQF and H can be made by entering a command
from a terminal board.
To do so, however, the frequency command forced switching function (input terminal function selection: 38)
needs to be set beforehand to an input terminal board.
If an OFF command is entered to the input terminal board: The command specified with HOQF will be
selected.
If an ON command is entered to the input terminal board: The command specified with H will be
selected.
2) Automatic switching by frequency command
Frequency priority selection parameter H =
The switching between the command specified with HOQF and H is done automatically according to
the frequency command entered.
If the frequency set with HOQF is above 1Hz: The command specified with HOQF will be selected.
If the frequency set with HOQF is 1Hz or less: The command specified with H will be selected.

Table of Contents

Other manuals for Toshiba TOSVERT VF-S11

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S11 and is the answer not in the manual?

Toshiba TOSVERT VF-S11 Specifications

General IconGeneral
ModelTOSVERT VF-S11
CategoryInverter
Output Frequency0.1-400Hz
Frequency Range0.1-400Hz
Control MethodV/f Control, Sensorless Vector Control
Power Rating0.2kW to 15kW
Cooling MethodForced air cooling
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationModbus RTU
Input Voltage200-240V, 380-480V
Braking UnitBuilt-in (optional external braking resistor)

Related product manuals