5.6 Standard default setting
V[R : Default setting
• Function
Allows setting of all parameters to the standard default setting, etc. at one time.
Note that HO, HOUN, H, H and H will not be reset to their factory default settings.
Title Function Adjustment range Default setting
V[R
Default setting
0: -
1: 50Hz default setting
2: 60Hz default setting
3: Standard default setting (Initializa-
tion)
4: Trip record clear
5: Cumulative operation time clear
6: Initialization of type information
7: Save user-defined parameters
8: Call user-defined parameters
9: Cumulative fan operation time rec-
ord clear
0
+ This function will be displayed as 0 during reading on the right. This previous setting is displayed.
Example:
+ V[R cannot be set during the inverter operating. Always stop the inverter first and then program.
Programmed value
Default setting (V[R = )
Setting V[R to will return all parameters to the standard values that were programmed at the factory.
, When 3 is programmed, <KP V
will be displayed for a short time after setting and will then be erased
and displayed the original indication 0.0. Trip history data will be cleared at this time.
Trip clear (V[R = )
Setting V[R to initializes the past four sets of recorded error history data.
, The parameter does not change.
Cumulative operation time clear (V[R = )
Setting V[R to resets the cumulative operation time to the initial value (zero).
Cumulative operation time clear (V[R = )
Setting V[R to clears the trips when an GV[R format error occurs. But if the GV[R displayed, call
us.