E6581158
F-80
6
6.21.6 Canceling the operation command
H : Canceling of operation command when standby terminal (ST) is turned
off
• Function
When the standby (ST) terminal is turned off during panel operation, the inverter will restart operation
if the ST terminal is turned back on. Using this parameter, you can also set the inverter so that, even
if the ST is turned back on, it will not restart operation until you press the RUN key.
Title Function Adjustment range Default setting
H
Canceling of operation
command when standby
terminal (ST) is turned off
0: Operation command canceled (cleared)
1: Operation command retained
1
6.21.7 Selection of operation panel stop pattern
H : Selection of operation panel stop pattern
• Function
This parameter are used to select a mode in which the motor started by pressing the RUN key on
the operation panel is stopped when the STOP key is pressed.
1) Slowdown stop
The motor slows down to a stop in the deceleration time set with FGE (or H or H).
2) Coast stop
The inverter cuts off power supply to the motor. The motor comes to a stop after coasting for a while by
inertia. Depending on the load, the motor may keep running for a good long time.
[Parameter setting]
Title Function Adjustment range Default setting
H
Selection of operation panel stop
pattern
0: Slowdown stop
1: Coast stop
0