E6581158
F-44
6
6.13.7 Canceling the operation command
H : Reverse-run prohibition
Function
This function prevents the motor from running in the forward or reverse direction when it receives the
wrong operation signal.
[Parameter setting]
Title Function Adjustment range Default setting
H
Reverse-run prohibition
0: Forward/reverse run permitted
1: Reverse run prohibited
2: Forward run prohibited
0
6.14 Drooping control
Hҏ : Drooping gain
Hҏ
: Drooping insensitive torque band
Function
These parameters are used to allow the motor to “slip” according to the load torque current. Using
these parameters, the dead zone torque and the gain can be adjusted.
[Parameter setting]
Title Function Adjustment range Default setting
H
Drooping gain 0-100% 0%
H Drooping insensitive torque band 0-100% 10%
Drooping gain
Insensitive torque current
Torque current

Table of Contents

Other manuals for Toshiba TOSVERT VF-S11

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S11 and is the answer not in the manual?

Toshiba TOSVERT VF-S11 Specifications

General IconGeneral
ModelTOSVERT VF-S11
CategoryInverter
Output Frequency0.1-400Hz
Frequency Range0.1-400Hz
Control MethodV/f Control, Sensorless Vector Control
Power Rating0.2kW to 15kW
Cooling MethodForced air cooling
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationModbus RTU
Input Voltage200-240V, 380-480V
Braking UnitBuilt-in (optional external braking resistor)

Related product manuals