6.19.4 Emergency stop
Hξ˜˜ξ˜’ξ˜•: Emergency stop
Hξ˜˜ξ˜’ξ˜–
: Emergency DC braking time
β€’ Function
These parameters allow you to specify how to stop operation using an external control device when
an external trip occurs. When operation is stopped, the trip G and the FL relay also are activated.
When setting Hξ˜˜ξ˜’ξ˜• to ξ˜” (emergency DC braking), set also Hξ˜”ξ˜—ξ˜“ (DC braking rate) and
Hξ˜˜ξ˜’ξ˜– (emergency braking time)
1) External trip stop via terminals
The external trip stop function can be executed via the a-contact. Proceed as follows to assign an
external stopping terminal and select the stopping method:
[Parameter setting]
Title Function Adjustment range Default setting
Hξ˜˜ξ˜’ξ˜• Emergency stop selection
0: Coast stop
1: Slowdown stop
2: Emergency DC braking
0
Hξ˜˜ξ˜’ξ˜– Emergency DC braking time 0.0 ~ 20.0 [sec] 1.0
Hξ˜”ξ˜—ξ˜“
DC braking current 0-100 (%) 50
(Example of terminal assignment): Assigning the trip stop function to the RES terminal
Title Function Adjustment range Setting
Hξ˜“ξ˜“ξ˜• Input terminal selection 3 (RES) 0-64
11 (External trip
stop)
Note 1) Emergency stopping via the specified terminal is possible, even during panel operation.
Note 2) If DC braking is not needed to bring the motor to a stop under normal conditions, although Hξ˜˜ξ˜’ξ˜• is
set to 2 (emergency DC braking), set the DC braking starting frequency (Hξ˜”ξ˜—ξ˜’) at 0.0 Hz.
2) Emergency stopping from the operation panel
Emergency stopping from the operation panel is possible
by pressing the STOP key on the panel twice while the inverter is not in the panel control mode.
(1) Press the STOP key............................. "GQHH" will blink.
(2) Press the STOP key once again.......... Operation will come to a trip stop in accordance with the setting
of the ξ˜‚Hξ˜˜ξ˜’ξ˜• parameter.
After this, "G" will be displayed and a failure detection signal
generated (FL relay deactivated).

Table of Contents

Other manuals for Toshiba TOSVERT VF-S11

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S11 and is the answer not in the manual?

Toshiba TOSVERT VF-S11 Specifications

General IconGeneral
ModelTOSVERT VF-S11
CategoryInverter
Output Frequency0.1-400Hz
Frequency Range0.1-400Hz
Control MethodV/f Control, Sensorless Vector Control
Power Rating0.2kW to 15kW
Cooling MethodForced air cooling
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationModbus RTU
Input Voltage200-240V, 380-480V
Braking UnitBuilt-in (optional external braking resistor)