E6581158
F-37
6
6.13.3 Retry function
H : Retry selection (Selecting the number of times)
Caution
Mandatory
Do not go near the motor in alarm-stop status when the retry function is selected.
The motor may suddenly restart, which could result in injury.
Take measures for safety, e.g. attach a cover to the motor, to prevent accidents if the motor suddenly
restarts.
Function
This parameter resets the inverter automatically when the inverter gives an alarm. During the retry
mode, the motor speed search function operated automatically as required and thus allows smooth
motor restarting.
[Parameter setting]
Title Function Adjustment range Default setting
H
Retry selection (number of
times)
0: None, 1-10 times 0
The likely causes of tripping and the corresponding retry processes are listed below.
Cause of tripping Retry process Canceling conditions
Momentary power
failure
Overcurrent
Overvoltage
Overload
Overheating
Up to 10 times in succession
1st retry: About 1 sec after tripping
2nd retry: About 2 sec after tripping
3rd retry: About 3 sec after tripping
10th retry: About 10 sec after tripping
The retry function will be canceled at
once if tripping is caused by an unusual
event other than: momentary power
failure, overcurrent, overvoltage or
overload.
This function will also be canceled if
retrying is not successful within the
specified number of times.
+ The retry function is disabled in the following unusual events:
QEC : Arm overcurrent at start-up GTT : Main unit RAM fault
QEN : Overcurrent on the load side at start-up GTT : Main unit ROM fault
GRJQ : Output phase failure GTT : CPU fault trip
QJ : External thermal trip GTT : Remote control error
QV : Overtorque trip GTT : Current detector fault
G : External trip stop GTT : Control circuit board format error
WE : Small-current operation trip GGR : EEPROM fault 1
WR : Undervoltage trip (main circuit) GGR : EEPROM fault 2
GH : Ground fault trip GGR : EEPROM fault 3
GRJ : Input phase failure GVP : Auto-tuning error
GV[R : Inverter type error G : VIA input detection error
G : Main unit CPU communication error
G : Excessive torque boost
G : CPU fault 2

Table of Contents

Other manuals for Toshiba TOSVERT VF-S11

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S11 and is the answer not in the manual?

Toshiba TOSVERT VF-S11 Specifications

General IconGeneral
ModelTOSVERT VF-S11
CategoryInverter
Output Frequency0.1-400Hz
Frequency Range0.1-400Hz
Control MethodV/f Control, Sensorless Vector Control
Power Rating0.2kW to 15kW
Cooling MethodForced air cooling
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationModbus RTU
Input Voltage200-240V, 380-480V
Braking UnitBuilt-in (optional external braking resistor)