6.19.10 Cumulative operation time alarm setting
H : Cumulative operation time alarm setting
Function
This parameter allows you to set the inverter so that it will put out an alarm signal after a lapse of the
cumulative operation time set with H.
* "0.1" displayed on the monitor refers to 10 hours, and therefore "1" denotes 100 hours.
Ex.: 38.5 displayed on the monitor = 3850 (hours)
Title Function Adjustment range Default setting
H
Cumulative operation time
alarm setting
0.0-9.999 610.0
Š Setting of output signal l
Ex.: When assigning the cumulative operation alarm signal output function to the OUT terminal
Title Function Adjustment range Setting
H
Output terminal selection 2A
(OUT-NO)
0-255
42 (negative
logic 43)
6.19.11 Over-voltage stall protection level
H : Over-voltage stall protection level
* For more details, see 6.13.5.