E6581158
F-16
6
Q Setting of switching terminals
The terminal for switching to motor 2 needs to be set, since this function is not assigned under the default
setting. Assign this function to an idle terminal.
The parameters to be switched depend on the particular identification number of the input terminal selection
function. (Refer to K-15.)
Input terminal function number
5
AD2
39
VF2
40
MOT2
58
AD3
61
OCS2
Parameters used and applicable parameters
OFF OFF OFF OFF OFF Default setting:
RV, XN, XNX, XD, VJT, CEE, FGE,
HU, H
ON OFF OFF OFF OFF
CEE ă HU, FGE ă HH ă
HU
- OFF OFF ON OFF
CEE ă HUFGE ă HH
ă HU
OFF OFF OFF OFF ON
H ă H
OFF ON OFF OFF OFF
RV ă XN ă HXNX ă
H
XD ă H, VJT ă H
- - ON OFF -
RV ă XN ă HXNX ă
HXD ă H, VJT ă
HH ă H, CEE ă
HUFGE ă HH ă
HU
6.5 Frequency priority selection
6.5.1 Using a frequency command according to the particular
situation
HOQF : Frequency setting mode selection 1
H
: Frequency priority selection
H
: Speed setting mode selection 2
Function
These parameters are used to switch between two types of frequency command signals.
Setting by parameters
Switching by frequency
Switching via terminal board input

Table of Contents

Other manuals for Toshiba TOSVERT VF-S11

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S11 and is the answer not in the manual?

Toshiba TOSVERT VF-S11 Specifications

General IconGeneral
ModelTOSVERT VF-S11
CategoryInverter
Output Frequency0.1-400Hz
Frequency Range0.1-400Hz
Control MethodV/f Control, Sensorless Vector Control
Power Rating0.2kW to 15kW
Cooling MethodForced air cooling
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationModbus RTU
Input Voltage200-240V, 380-480V
Braking UnitBuilt-in (optional external braking resistor)