E6581158
F-27
6
6.8 Auto-stop in case of lower-limit frequency continuous
operation
6.8.1 Auto-stop in case of lower-limit frequency continuous
operation
H : Auto-stop in case of lower-limit frequency continuous operation
Function
If operation is carried out continuously at a frequency below the lower-limit frequency (NN) for the period
of time set with H, the inverter will automatically slow down the motor to a stop. At that time,
NUVR” is displayed (alternately) on the operation panel.
This function will be canceled if a frequency command above the lower-limit frequency (NN).
[Parameter setting]
Title Function Adjustment range Default setting
H
Auto-stop in case of lower-limit fre-
quency continuous operation time
0.0: None
0.1-600.0 (sec.)
0.0
Note: This function is enabled even at the start of operation and during switching between forward and re-
verse run.
Output frequency [Hz]
NN+0.2Hz
NN
Operation signal (F-CC)
Time [s]
H
ON
OFF
HH

Table of Contents

Other manuals for Toshiba TOSVERT VF-S11

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S11 and is the answer not in the manual?

Toshiba TOSVERT VF-S11 Specifications

General IconGeneral
ModelTOSVERT VF-S11
CategoryInverter
Output Frequency0.1-400Hz
Frequency Range0.1-400Hz
Control MethodV/f Control, Sensorless Vector Control
Power Rating0.2kW to 15kW
Cooling MethodForced air cooling
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationModbus RTU
Input Voltage200-240V, 380-480V
Braking UnitBuilt-in (optional external braking resistor)

Related product manuals