5.12 Manual torque boost - increasing torque boost at low
speeds
XD : Torque boost 1
Function
If torque is inadequate at low speeds, increase torque by raising the torque boost rate with this
parameter.
Output voltage
[V]/(%)
Base frequency voltage
Output frequency (Hz)
XD
Base frequency XN
XNX
[Parameters]
Title Function Adjustment range Default setting
XD Torque boost 1 0.0 - 30.0 (%)
According to model
(See Chapter 11, K-14 )
+ Valid when RV is set to (V/F constant) or (square reduction)
Note 1: The optimum value is programmed for each inverter capacity. Be careful not to increase the torque boost
rate too much because it could cause an overcurrent trip at startup.
5.13 Setting the electronic thermal
VJT: Motor electronic-thermal protection level 1
QNO
: Electronic thermal protection characteristic selection
Function
This parameter allows selection of the appropriate electronic thermal protection characteristics according
to the particular rating and characteristics of the motor.