EasyManuals Logo

Toshiba TOSVERT VF-S11 User Manual

Toshiba TOSVERT VF-S11
269 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #107 background imageLoading...
Page #107 background image
E6581158
F-5
6
6.2 Input signal selection
6.2.1 Priority selection (both F-CC, R-CC are ON)
H : Priority selection (both F-CC, R-CC are ON)
Function
This parameter allows you to select the direction in which the motor runs when a forward run (F)
command and a reverse run (R) command are entered simultaneously.
1) Reverse
2) Slowdown stop
Q Parameter setting
Title Function Adjustment range Default setting
H
Priority selection (both F-CC, R-CC
are ON)
0: Reverse
1: Slowdown stop
1
[H = (Stop)]: If an F command and an R command are entered simultaneously,
the motor will slow down to a stop.
Forward run
Reverse run
Run forward signal
Run backward signal
ON
OFF
ON
OFF
Output frequency [Hz]
Set frequency
Time[s]0

Table of Contents

Other manuals for Toshiba TOSVERT VF-S11

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S11 and is the answer not in the manual?

Toshiba TOSVERT VF-S11 Specifications

General IconGeneral
ModelTOSVERT VF-S11
CategoryInverter
Output Frequency0.1-400Hz
Frequency Range0.1-400Hz
Control MethodV/f Control, Sensorless Vector Control
Power Rating0.2kW to 15kW
Cooling MethodForced air cooling
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationModbus RTU
Input Voltage200-240V, 380-480V
Braking UnitBuilt-in (optional external braking resistor)