E6581158
E-7
5
5.3 Specifying an operation mode, using parameters
C
CC
CW
WW
W
: Automatic function setting
Function
Automatically programs all parameters (parameters described below) related to the functions by selecting
the inverter's operating method.
The major functions can be programmed simply.
[Parameter setting]
Title Function Adjustment range Default setting
CW
Automatic function setting
0: Disabled
1: Coast stop
2: 3-wire operation
3: External input UP/DOWN setting
4: 4-20mA current input operation
0:
Automatically programmed functions and parameter set values
Default setting 1: Coast stop 2: 3-wire opera-
tion
3: External input
UP/DOWN set-
ting
4: 4-20mA
current input
operation
EOF
1: Operation
panel
0: Terminal board 0: Terminal board 0: Terminal board 0: Terminal board
HOF
0: Potentiometer 0: Potentiometer 0: Potentiometer
5: UP/DOWN
from external
contact
1: VIA
H (Always) 1: ST 0: Disabled 1: ST 1: ST 1: ST
H (F) 2:F 2:F 2:F 2:F 2:F
H (R) 3:R 3: 3:R 3:R 3:R
H (RES) 10: RES 10: RES 10: RES 10: RES 10: RES
H (S1) 6: SS1 6: SS1 6: SS1 41:UP 6: SS1
H (S2) 7: SS2 7: SS2 7: SS2 42: DOWN 7: SS2
H (S3) 8: SS3 1: ST 49: HD 43: CLR 38: FCHG
H 0 (%) - - - 20 (%)
Note) See K-15 for input terminal functions.
Disabled (CW=)
Input terminals and parameters are standards programmed at the factory.
Coast stop (CW=)
Setting for coast stopping. In sink logic mode, closing the circuit between the S3 and CC terminals places
the inverter in standby mode and opening the circuit places it in coast stop mode, because ST (standby sig-
nal) is assigned to the S3 terminal.

Table of Contents

Other manuals for Toshiba TOSVERT VF-S11

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S11 and is the answer not in the manual?

Toshiba TOSVERT VF-S11 Specifications

General IconGeneral
ModelTOSVERT VF-S11
CategoryInverter
Output Frequency0.1-400Hz
Frequency Range0.1-400Hz
Control MethodV/f Control, Sensorless Vector Control
Power Rating0.2kW to 15kW
Cooling MethodForced air cooling
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationModbus RTU
Input Voltage200-240V, 380-480V
Braking UnitBuilt-in (optional external braking resistor)