6.13.2 Regenerative power ride-through control/Deceleration
stop
H : Regenerative power ride-through control/Deceleration stop
Function
1) Regenerative power ride-through control continues the operation of the motor by utilizing motor
regenerative energy in the event of momentary power failure.
2) Slowdown stop in the event of momentary power failure: If a momentary power failure occurs dur-
ing operation, the inverter stops forcibly. (Deceleration time varies with control.) When operation is
stopped, the message “UVQR” is displayed (alternately) on the operation panel.
After the forced stop, the inverter remains static until you put off the operation command momen-
tarily.
[Parameter setting]
Title Function Adjustment range Default setting
H
Regenerative power ride-through control /
Deceleration stop
0: Disabled
1: Enabled
2: Slowdown stop
0
Note: Even when this parameter is set, the particular load conditions may cause the motor to coast. In this
case, use the auto-restart function H along with this parameter function.
[When power is interrupted]
Motor speed
About 100ms
Input voltage
* The time for which the operation of the motor can be
continued depends on the machine inertia and load
conditions. Before using this function, therefore,
perform verification tests.
[If momentary power failure occurs]
M
otor speed
Input voltage

Table of Contents

Other manuals for Toshiba TOSVERT VF-S11

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S11 and is the answer not in the manual?

Toshiba TOSVERT VF-S11 Specifications

General IconGeneral
ModelTOSVERT VF-S11
CategoryInverter
Output Frequency0.1-400Hz
Frequency Range0.1-400Hz
Control MethodV/f Control, Sensorless Vector Control
Power Rating0.2kW to 15kW
Cooling MethodForced air cooling
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationModbus RTU
Input Voltage200-240V, 380-480V
Braking UnitBuilt-in (optional external braking resistor)

Related product manuals