E6581158
F-19
6
Q Parameter setting
Title Function Adjustment range Default setting
H
VIA input point 1 setting 0-100 (%) 0
H VIA input point 1 frequency 0.0-500.0 (Hz) 0.0
H
VIA input point 2 setting 0-100 (%) 100
H
VIA input point 2 frequency 0.0-500.0 (Hz)
50.0 (WP type)
60.0 (WN, AN type)
H
VIB input point 1 setting 0-100 (%) 0
H VIIB input point 1 frequency 0.0-500.0 (Hz) 0.0
H VIB input point 2 setting 0-100 (%) 100
H VIB input point 2 frequency 0.0-500.0 (Hz)
50.0 (WP type)
60.0 (WN, AN type)
H
Point 1 setting 0-100 (%) 0
H
Point 1 frequency 0.0-500.0 (Hz) 0.0
H
Point 2 setting 0-100 (%) 100
H Point 2 frequency 0.0-500.0 (Hz) 60.0
Note 1: Don't set the same value between point 1 and point 2. If set the same falue, the GTT is displayed.
1) 0-10Vdc voltage input adjustment (VIA, VIB)
VIA, VIB terminals
ȷThe output frequency with
respect to the voltage input is
adjusted according to the
selected reference point.
ȷGradient and bias can be set
easily.
H
HH
H
H
HH
H
100 (%)
voltage signal
H
HH
H
H
HH
H
0 ( Hz)
H
HH
H
H
HH
H
0 (%)
H
HH
H
H
HH
H
60 ( Hz )
0
2) 4-20mAdc current input adjustment (VIA: VIA slide switch in the I position)
VIA terminal
ȷThe output frequency with respect to
the current input is adjusted
according to the selected reference
point.
ȷGradient and bias can be set easily.
ȷSet H to to create a current
input from 0 to 20mA.
H
HH
H
100 (%)
20mA current signal
H
HH
H
0 ( Hz)
H
HH
H
20 (%)
4
H
HH
H
60 ( Hz )