<<Sample sequence diagram 2: Adjustment with pulse signals>>
RUN command (such as F)
Increasing (UP) signal
Decrementing (DOWN) signal
Set frequency clearing signal
Upper limit frequency
Command frequency (Hz)
(The dotted lines represent
effective output frequencies.)
Q If two signals are impressed simultaneously
• If a clear single and an up or down signal are impressed simultaneously, priority will be given to the
clear signal.
• If up and down signals are impressed simultaneously, The frequency will change at the specified up
or down rate.
Q About the setting of the initial up/down frequency
To adjust the frequency starting at a specified frequency other than 0.0 Hz (default initial frequency)
after turning on the inverter, specify the desired frequency using H (initial up/down frequency).
Q About the change of the initial up/down frequency
To make the inverter automatically save the frequency immediately before it is turned off and start
operation at that frequency next time power is turned on, set H (change of initial up/down
frequency) to 1 (which changes the setting of H when power is turned off).
Keep in mind that the setting of H is changed each time power is turned off.
Q Frequency adjustment range
The frequency can be set from 0.0Hz to HJ (Maximum frequency). The lower-limit frequency will be
set as soon as the set frequency clearing function (function number 43, 44) is entered from the input
terminal.