E6581158
F-67
6
6.19.9 Over-torque trip
H : Over-torque trip/alarm selection
H
: Over-torque detection level
H
: Over-torque detection time
H
: Over-torque detection level hysteresis
Function
Use the  parameter to trip the inverter or to output the alarm if a torque currrent exceeding the
H-specified level flows for more than the H-specified time. Trip information is displayed
as "QV".
H=: .......... No tripping (FL relay deactivated).
An over-torque alarm can be put out by setting the output terminal function selection
parameter.
H=: .......... The inverter is tripped (FL relay activated) only after a torque current exceeding the
H-specified level has been detected for more than the H-specified time.
Title Function Adjustment range Default setting
H
Over-torque trip/alarm selection
0: Alarm only
1: Tripping
0
H Over-torque detection level 0-250 (%) 150
H
Over-torque detection time 0.0-10.0 [sec] 0.5
H Over-torque detection level hysteresis 0-100 (%) 10

Table of Contents

Other manuals for Toshiba TOSVERT VF-S11

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S11 and is the answer not in the manual?

Toshiba TOSVERT VF-S11 Specifications

General IconGeneral
ModelTOSVERT VF-S11
CategoryInverter
Output Frequency0.1-400Hz
Frequency Range0.1-400Hz
Control MethodV/f Control, Sensorless Vector Control
Power Rating0.2kW to 15kW
Cooling MethodForced air cooling
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationModbus RTU
Input Voltage200-240V, 380-480V
Braking UnitBuilt-in (optional external braking resistor)

Related product manuals